Answer by Harper - Reinstate Monica for Is there a safe and compliant way to...

Yes.You can run an isolated electrical line, using normal in-wall wiring methods, from a single inlet to outlets.The inlet will need to be in the NEMA family. A C13 inlet won't cut it for at least 2...

View Article



Image may be NSFW.
Clik here to view.

Is there a safe and compliant way to run consumer UPS power through house...

I would like to remove an existing cable from the breaker panel, that feeds a single home run outlet, and wire it to a consumer UPS that I will locate near the panel, through a junction...

View Article

Image may be NSFW.
Clik here to view.

Answer by jay613 for Is there a safe and compliant way to run consumer UPS...

Here I'm planning a nice implementation of the advice in the accepted answer. This plan provides raw and UPS power to the basement location and also through existing house wiring to a den outlet. It...

View Article

Answer by Guest for Is there a safe and compliant way to run consumer UPS...

You could install one of these upstream of the outlet: https://ezgeneratorswitch.comI am not affiliated with them in any way.